T3A-V2.0 Solution
Chapter 1 Basics
Wiring
R.S.T power cord wiring explanation
(1) Three-phase AC220V wiring: Connect the three power lines to R.S.T. (*Connect the ground line to PE);
(2) Single-phase AC220V wiring: Connect the live wire to R and the neutral wire to T (*Connect the ground wire only to PE. Connecting it to other points may burn the driver);
(3) Three-phase four-wire AC380V wiring: Connect the three live wires to R.S.T. and the ground wire to PE. Connecting it to other points may burn the driver.
*Note: Before wiring, be sure to determine whether the driver is AC220V or AC380V.
(4) P and BK wiring: Connect the external brake resistor. *Not connected by default
If frequent starting and stopping or heavy load is required, please configure the resistor correctly according to the manual.
Note: The power line cannot be connected here, otherwise the driver will burn out.

U.V.W motor connection line explanatio
(2) The motor wires U, V, W, and PE must be connected correctly to the corresponding drive. If the U, V, and W phases are connected incorrectly, the motor will not operate properly. If the PE phases are connected incorrectly, the motor may burn out or cause electric shock.

CN2 encoder line explanation
(2) After plugging the encoder cable into the CN2 port of the driver, tighten the two screws next to it.

CN1 control line explanation
(1) If the control line needs any function, you can ask the manufacturer to solder it or you can solder it yourself;
(2) Pay attention to the difference between 5V and 24V signals on the control line. If you use a 5V signal and the control line is soldered to 24V, it will cause the internal components of the driver to burn out. The same applies to using a 5V control line with a 24V signal;
(3) If the pulse signal is 5V and the control line is 24V, you can disassemble the control line, find pins 8 and 9, and solder a 2K resistor to each pin to ensure normal use. The same applies to using a 5V control line with a 24V signal. The 2K resistor will be provided with the terminal block in the accessory bag when it leaves the factory.
Pin 31: 24V power input; for example, if you need to use DI1-DI6 input signals, pin 31 must be connected to a 24V switching power supply; otherwise, the input will be deenergized. This means that DI1-DI6 require an external 24V power supply.
Pin 16: Servo Enable (DI1); After soldering this pin, an external enable is provided. The driver automatically enables when a signal is received from DI1.
Pin 39: 24V pulse signal; when Pulse+ and Direction+ are connected to pins 38 and 39, respectively, the control line is 24V.
Pin 38: 24V Direction signal; Pulse+, When Direction+ is connected to pins 38 and 39, the control line is 24V.
Pin 25: 5V pulse signal; when Pulse+ and Direction+ are connected to pins 24 and 25, respectively, the control line is 5V.
Pin 24: 5V direction signal; when Pulse+ and Direction+ are connected to pins 24 and 25, respectively, the control line is 5V.
Pin 9: Pulse signal negative; whether the control line is 24V or 5V is determined by pins 24, 25, 38, and 39.
Pin 8: Direction signal negative; whether the control line is 24V or 5V is determined by pins 24, 25, 38, and 39.

Buttons
Button Detailed Introduction

Parameters
Introduction to common parameters
P-002: Motor Code (This parameter specifies the motor model. Enter the code corresponding to the motor model here. If this parameter is incorrectly set, the motor may make unusual noises or vibrate. Before setting this parameter, change the operation password to 316; otherwise, the parameter cannot be modified. After changing this parameter, execute E-DEF to save the change (it takes effect after a power cycle).
P-098: Enable (The RUN light on the panel indicates the drive is enabled, indicating P-098 = 1 or the external enable is on. (P-098 = 1 indicates enabled, P-098 = 0 indicates disabled.)
Parameter setting method

To set the motor code and restore to factory settings:
a. Change parameter P-000 to 316;
b. Change parameter P-002 to the corresponding motor code;
c. Turn off the enable (P-098 = 0) or remove the CN1 connector. The RUN light will be off, indicating no enable.
d. Find E-DEF and press and hold the Enter key until the "done" display appears. Power off and restart, as shown in the figure:


Common Problems and Solutions
1. Unable to modify P-002 parameters. Factory reset results in "Error":
a. Disconnect the enable function: Remove the CN1 control head for external enable. Internal enable function P-098 = 0. If P-100 = -1, change it to P-100 = 1, save the settings, and power cycle. If the RUN indicator or the leftmost decimal point is off, the function is not enabled.
b. If P-000 = 316, press the E or Enter key to confirm.
c. Modify P-002 to the value corresponding to the motor table and confirm.
d. Enter the "E" parameter group, find "E-DEF," and press and hold E or Enter for 3 seconds until "donE" appears.
e. Power cycle the function until no display appears. The factory reset is successful, and the motor code is successfully set.
2. The motor makes unusual noises, vibrates, or jumps when the servo is enabled:
a. Check that the P-002 motor code corresponds to the motor. Reset the motor code and restore to factory settings.
b. Reduce P-005 appropriately to see if this works.
c. Reduce P-087 appropriately: when P-087=751, change it to Pr087=451; when P-087=451, change it to Pr087=300.
Internal mode wiring and parameters
Internal multi-speed

T3A multi-speed setting
P-004=1 Speed mode
P-025=1 Internal multi-speed
P-101=10 Speed 1
P-102=11 Speed 2
P-103=12 Speed 3
P-098=0 External enable controlled by DI1(16)
P-098=1 Internal forced enable, motor shaft locked
If DI2-DI4 are both off, the motor will run at speed P-137.
If DI2 is on, the motor will run at speed P-138.
If DI3 is on, the motor will run at speed P-139.
If DI2 and DI3 are on, the motor will run at speed P-140.
If DI4 is on, the motor will run at speed P-141.
If DI2 and DI4 are on, the motor will run at speed P-142.
If DI3 and DI4 are on, the motor will run at speed P-143.
If DI2 and DI4 are on simultaneously, the motor will run at speed P-144.
Note: A positive value between Pr137 and Pr144 indicates forward rotation, while a negative value indicates reverse rotation.
Internal multi-stage torque

T3A multi-stage torque setting
P-004=2 Torque mode
P-026=1 Internal multi-stage torque
P-101=13 Torque 1
P-102=14 Torque 2
P-098=0 External enable controlled by DI1(16)
P-098=1 Internal forced enable, motor shaft locked
Four Torque Ranges
When D1 is on, the motor locks the shaft;
When both D12 and D13 are off, the motor operates at P-145 torque;
When D12 is on, the motor operates at P-146 torque;
When D13 is on, the motor operates at P-147 torque;
When both D12 and D13 are on, the motor operates at P-148 torque.
Note: A positive value between Pr137 and Pr144 indicates forward rotation, while a negative value indicates reverse rotation.
Chapter 2 Intermediate
Various alarm articles
1. Servo displays "Err9," "Err10," or "Err32" upon power-up.
a. Check the encoder cable for any modifications, ensure proper contact between the encoder cable connector pins, and check for any water or debris in the connector.
b. Encoder disconnection: Check the D-COD signal (corresponding to the UVWZBA signal). Rotate the motor shaft; UVWBA must not be simultaneously 1 or 0. If no change occurs during rotation, the signal is incorrect. Replace the motor or encoder cable.
c. Shielding the alarm:
2. Servo displays "Err4" during operation
a. Check that the motor and motor code match;
b. Check that the speed reduction is normal, the electronic gear ratio is correct, and the speed exceeds the rated motor speed;
c. Check the encoder and motor cables, especially the motor cables for loose contact;
d. Check the motor and mechanical load for any jams;
e. Increase the position tolerance detection range parameter in P-080;
f. If the above tests are normal, but the "Err4" alarm persists during operation, increase P-093 (default 100) to 130-150 and retest;
g. If the alarm persists after the above steps, consult with the equipment manufacturer to modify the configuration.
3. The servo displays "Err6" during operation.
a. Check that the motor and motor code match.
b. Check that the U, V, and W phase sequences are correct.
c. Check that the load is not stuck.
4. Servo displays "Err11" during operation.
a. Disconnect the power cable and re-power on to see if "Err11" is displayed. If the alarm persists, replace the driver. If it does not, check the power cable and motor.
b. Interchange the motor and driver to determine the problem.
5. Servo operation reports "Err12"
a. Check that the motor code is set correctly.
b. Check if the load is excessive, causing an overcurrent alarm.
6. Servo displays "Err29" during operation.
a. Check if the external load is stuck.
b. Check the motor code and P-070/071.
a. "Err5" indicates that the host computer is sending pulse commands too quickly, exceeding the motor's response capacity. We recommend increasing the host computer's acceleration/deceleration times or increasing the position command smoothing time (P-040) by 10 steps.
b. If the above measures are ineffective or the host computer cannot be modified, set P-116 to 32 to disable the "Err5" alarm.
8. "Err2" or "Err14" appears during drive startup.
a. If the alarm occurs due to frequent acceleration and deceleration with high inertia, first check the monitoring menus d-I and d-PI to see if the instantaneous and maximum current values exceed the allowable ranges for the drive and motor. If so, reduce the inertia acceleration accordingly (in speed mode: increase the acceleration time P-060 and deceleration time P-061; in position mode: increase the acceleration and deceleration times on the host controller) to control the current within the allowable ranges for the drive and motor, and check whether the fault disappears.
b. Check if the power supply voltage is too high.
c. Power off for a while and then power on again to see if the alarm reappears.
d. Install an external braking resistor at the P and BK terminals.
e. If the above methods are ineffective, return the product to the factory for inspection.
Parameter Adjustment
1. Rigidity Parameters:
When the motor code is correct, adjust the following parameters if the motor is experiencing unusual noise or vibration.
P-005: This parameter is generally adjusted for motor vibration when using a lead screw or helical gear. Set this parameter to approximately 90° for lead screws and approximately 100° for helical gears, with a range of 5° increments and deflections.
P-009: This parameter is generally adjusted for motor vibration when using a lead screw or helical gear. Set this parameter to approximately 80° for lead screws and approximately 20° for helical gears, with a range of 5° increments and deflections.
P-006: This parameter is generally adjusted for motor vibration when using a belt or chain. The longer the belt or chain, the higher the value; a setting of approximately 200-300° is generally recommended.
P-019: This parameter is generally adjusted for motor vibration when using a belt or chain. The longer the belt or chain, the higher the value; a setting of approximately 300° is generally recommended.
2. Electronic Gear Ratio:
P-029: Electronic Gear Ratio Numerator
P-030: Electronic Gear Ratio Denominator
P-029 = 10000
P-030 = Number of pulses required for one revolution
For example, if 4000 pulses are required for one revolution:
P-029 = 10000
P-030 = 4000
Reduced to:
P-029 = 5
P-030 = 2
1. Check the power and encoder cables for loose connections or broken wires.
2. Check the motor code settings for correctness.
3. Check the control mode and command source settings for correctness.
4. Check the gain parameters for proper settings.
5. If possible, swap the drive to troubleshoot the problem.
6. Check the motor.
Chapter 3 Practical Combat
a. Check the pulse and direction wiring for correct operation.
b. If the host computer is a PLC, connect it to a 24V port or add a 2K resistor, with the pulse and direction wiring connected separately.
2. The servo's reciprocating motion deflects in one direction, and its repeated positioning deflects in another direction. When powered on, the enable signal is enabled but no pulses are sent. The motor runs at a constant speed:
Check "d-cpo" -- "lo" -- "****" to see if the value changes. Check "d-frq" -- "f**.*" to see if there are any changes.
a. Control cable shield:
(1). If shielded, disconnect both ends.
(2). Connect the servo to the CN1 housing and the host computer to digital ground (PLC to 0V power supply).
a. Increase P-038 (usually = 6 for PLCs), save, and restart.
b. Change the pulse type to AB pulse.
c. The servo motor brake is not open, which can easily damage the brake.
d. The brake cable must be connected to a relay. The default is normally open, so ensure correct wiring. By default, 24V is connected to the positive terminal of the relay coil, D04 is connected to the negative terminal of the relay coil, and the common point is connected to the 0V terminal of the switching power supply.
e. The brake cannot be used for deceleration.
a. Check the power supply voltage to see if it matches the drive voltage.
b. Connect the power supply only, leaving the encoder and motor cables disconnected. Restart the servo and see if the display is normal. If not, return the servo to the factory for inspection.
a. Check the motor code.
b. Adjust the stiffness. Experienced values: P-005 = 95, P-009 = 90.
a. Check the motor code.
b. Adjust the rigidity parameters. Experienced values: P-005 = 95, P-006 = 300 (The longer the chain and belt, the higher the value). P-009 = 20, P-019 = 150 (The longer the chain and belt, the higher the value).
b. Ensure wiring is correct.
c. P-181, P-182, P-183. Parameters must be set correctly and saved after a power cycle to take effect.
d. Monitor the D-R E
rE-12: Number of successful communications.
rE-13: Number of communication errors. If this value continues to increase, check the communication parameters and ensure they are consistent with those on the host computer.
a. Parameter P-097 = 0.
b. The forward and reverse limit settings must be correctly configured. DI terminal function codes 3/4 are low-voltage normally closed signals, and -3/-4 are normally open signals.
c. If "Err7" occurs, change P-116 to 136, save the settings, and then power cycle.
a. Change P-100 to -1;
b. Use external enable;
a. Modify the following parameters: P-005 = 110, P-006 = 100, P-009 = 95, P-021 = 50, P-022 = 60.
If the motor experiences unusual noise or vibration after the parameters are modified, reduce P-005 and P-009 appropriately.
b. Increase the acceleration and deceleration times.
T3D-V2.0 Solution
Chapter 1 Basics
Wiring
L1.L2 power line wiring instructions
(2) Braking resistor connection and usage instructions: If using the internal braking resistor, short-circuit terminals P and D, and it will work normally according to the factory settings, as shown in the figure below. If using an external braking resistor, you must first remove the short-circuit metal sheet between P and D, and then connect the external braking resistor across terminals P and C, as shown in the figure below.

U.V.W motor connection line explanation:
(2) The motor wires U, V, W, and PE must be connected correctly to the corresponding drive. If the U, V, and W phases are connected incorrectly, the motor will not operate properly. If the PE phase is connected incorrectly, the motor may burn out or cause electric shock.

CN2 encoder line explanation
(2) Plug the encoder cable into the CN2 port of the driver.

CN1 control line explanation
(2) When using the control line, pay attention to the difference between 5V and 24V signals. If you use a 5V signal and the control line is soldered to 24V, it will cause the internal components of the driver to burn out. The same applies to using a 5V control line with a 24V signal.
(3) If the pulse signal is 5V and the control line is 24V, you can disassemble the control line, find pins 8 and 9, and solder a 2K resistor to each pin. The 2K resistor will be provided with the terminal block in the accessory bag when it leaves the factory.
Note: The label on the control line provided by the manufacturer will indicate 24V or 5V.
CN1 common pin definition
Pin 31: 24V power input; for example, if you need to use DI1-DI6 input signals, pin 31 must be connected to a 24V switching power supply; otherwise, the input will be deenergized. This means that DI1-DI6 require an external 24V power supply.
Pin 16: Servo Enable (DI1); After soldering this pin, external enable is provided. The driver automatically enables when a signal is received from DI1.
Pin 39: 24V pulse signal; when Pulse+ and Direction+ are connected to pins 38 and 39, respectively, the control line is 24V.
Pin 38: 24V Direction signal; Pulse+, When Direction+ is connected to pins 38 and 39, the control line is 24V.
Pin 25: 5V pulse signal; when Pulse+ and Direction+ are connected to pins 24 and 25, respectively, the control line is 5V.
Pin 24: 5V direction signal; when Pulse+ and Direction+ are connected to pins 24 and 25, respectively, the control line is 5V.
Pin 9: Pulse signal negative; whether the control line is 24V or 5V is determined by pins 24, 25, 38, and 39.
Pin 8: Direction signal negative; whether the control line is 24V or 5V is determined by pins 24, 25, 38, and 39.

Buttons
Button Detailed Introduction

![]()
Introduction to common parameters
P-002: Motor Code (This parameter specifies the motor model. Enter the code corresponding to the motor model here. If this parameter is incorrectly set, the motor may make unusual noises or vibrate. Before setting this parameter, change the operation password to 316; otherwise, the parameter cannot be modified. After changing this parameter, execute E-DEF to save the change and power it on again.)
P-098: Enable (The first decimal point on the digital tube, lit from left to right, indicates the drive is enabled, indicating P-098 = 1 or the external enable is on. P-098 = 1 indicates enabled, while P-098 = 0 indicates disabled.)
Parameter setting method
Take modifying P-098 (enable) as an example

a. Change parameter P-000 to 316
b. Turn off the enable (P-098 = 0) or remove the CN1 connector. The RUN light will be off, indicating no enable.
c. Find E-DEF and press and hold the OK button until the "done" display appears. Power off and restart, as shown in the figure:

,Common Problems and Solutions
a. Disconnect the enable function: Remove the CN1 control head for external enable. Internal enable function P-098 = 0. If P-100 = -1, change it to P-100 = 1, save, and power cycle. If the RUN indicator or the leftmost decimal point is off, the function is not enabled.
b. If P-000 = 316, press the E or Enter key to confirm.
c. Modify P-002 to the value corresponding to the motor table and confirm.
d. Enter the "E" parameter group, find "E-DEF," press and hold E or Enter for 3 seconds, and "donE" will appear.
e. Power cycle the function until no display appears. The factory reset is successful, and the motor code is successfully set.
a. Check that the P-002 motor code matches the motor. Reset the motor code and restore to factory settings.
b. Reduce P-005 to see if it works.
c. Reduce P-210 to 60.
Internal mode wiring and parameters
Internal multi-speed

P-004 = 1 Speed Mode
P-025 = 1 Internal Multi-Speed
P-101 = 10 Speed 1
P-102 = 11 Speed 2
P-103 = 12 Speed 3
If DI1 is on, the motor locks the shaft.
If neither DI2 nor DI4 is on, the operation will be at speed P-137.
If DI2 is on, the operation will be at speed P-138.
If DI3 is on, the operation will be at speed P-139.
If both DI2 and DI3 are on, the operation will be at speed P-140.
If DI4 is on, the operation will be at speed P-141.
If DI2 and DI4 are on, the operation will be at speed P-142.
If DI3 and DI4 are on, the operation will be at speed P-143.
If both DI2 and DI4 are on, the operation will be at speed P-144.
Note: Positive values between P-137 and P-144 indicate forward rotation, while negative values indicate reverse rotation.
Internal multi-stage torque

P-026 = 1 Internal multi-stage torque
P-101 = 13 Torque 1
P-102 = 14 Torque 2
P-098 = 0 External enable controlled by DⅠ1(16)
P-098 = 1 Internal forced enable, motor shaft locked
Four Torque Levels
When DI1 is on, the motor locks the shaft.
When neither DI2 nor DI3 is on, the operation is based on P-145 torque.
When DI2 is on, the operation is based on P-146 torque.
When DI3 is on, the operation is based on P-147 torque.
When both DI2 and DI3 are on, the operation is based on P-148 torque.
Note: A positive value between P-145 and P-148 indicates forward rotation, while a negative value indicates reverse rotation.
Chapter 2 Intermediate
Various alarm articles
a. Change P-000 to 510, find A-fn, and press and hold to clear the alarm.
b. For multi-turn absolute encoder motors, the encoder cable must be connected to a battery.
a. Check the encoder cable for any modifications, ensure proper contact between the encoder cable connector pins, and check for any water or debris in the connector.
b. Encoder cable disconnection: Check the D-COD signal (corresponding to the UVWZBA signal). Rotate the motor shaft; UVWBA must not be simultaneously 1 or 0. If no change occurs during rotation, the signal is incorrect. Replace the motor or encoder cable.
a. Check the motor and motor code.
b. Check the speed reduction is normal: Is the electronic gear ratio correct? Does the speed exceed the rated motor speed?
c. Check the encoder and motor cables, especially the motor cables, for loose contact.
d. Check the motor and mechanical load for any jams.
e. Increase the position tolerance detection range parameter in P-080.
f. If the above tests are normal, but the "Err4" alarm persists during operation, increase P-093 (default 100) to 130-150 and retest.
g. If the alarm persists after the above steps, consult with the equipment manufacturer to modify the configuration.
a. Check that the motor and motor code match.
b. Check that the U, V, and W phase sequences are correct.
c. Check that the load is not stuck.
a. Disconnect the power cable and re-power on to see if "Err11" is displayed. If the alarm persists, replace the driver. If it does not, check the power cable and motor.
b. Interchange the motor and driver to determine the problem.
a. Check if the external load is stuck.
b. Check the motor code and P-070/071.
a. "Err5" indicates that the host computer is sending pulse commands too quickly, exceeding the motor's response capacity. We recommend increasing the host computer's acceleration/deceleration times or increasing the position command smoothing time (P-040) by 10 steps.
b. If the above measures are ineffective or the host computer cannot be modified, set P-116 to 32 to disable the "Err5" alarm.
a. If the alarm occurs due to frequent acceleration and deceleration with high inertia, first check the monitoring menus d-I and d-PI to see if the instantaneous and maximum current values exceed the allowable ranges of the drive and motor. If so, reduce the inertia acceleration accordingly (in speed mode: increase the acceleration time P-060 and deceleration time P-061; in position mode: increase the acceleration and deceleration times on the host controller) to control the current within the allowable range of the drive and motor, and check whether the fault disappears.
b. Check if the power supply voltage is too high.
c. Power off for a longer period and then power on again to see if the alarm reappears.
d. If the above methods are ineffective, return the product to the factory for inspection.
a. Operate with the motor unloaded.
Change P-000 to 620
Change P-002 to the corresponding code.
Change P-099 to 5-AN5.
Save the data, power off, and restart.
After restarting, find A-fn -1, press and hold to confirm. "Done" will appear. Return.
Find fn -2, press and hold to confirm. Return. Find P-000, change it to 610, save the data, power off, and restart.
Parameter Adjustment
When the motor code is correct, adjust the following parameters if the motor is experiencing unusual noise or vibration.
P-005: This parameter is generally adjusted for motor vibration when using a lead screw or helical gear. Set this parameter to approximately 90° for lead screws and approximately 100° for helical gears, with a range of 5° increments and deflections.
P-009: This parameter is generally adjusted for motor vibration when using a lead screw or helical gear. Set this parameter to approximately 80° for lead screws and approximately 20° for helical gears, with a range of 5° increments and deflections.
P-006: This parameter is generally adjusted for motor vibration when using a belt or chain. The longer the belt or chain, the larger the value. A setting of approximately 200-300° is generally recommended.
P-019: This parameter is generally adjusted for motor vibration when using a belt or chain. The longer the belt or chain, the larger the value. A setting of approximately 300° is generally recommended.
P-029: Electronic Gear Ratio Numerator
P-030: Electronic Gear Ratio Denominator
P-029 = 10000
P-030 = Number of pulses required for one revolution. For example, 4000 pulses.
One revolution:
P-029 = 10000
P-030 = 4000
Reduced to:
P-029 = 5
P-030 = 2
Basic service process
2. Check the motor code settings for correctness.
3. Check the control mode and command source settings for correctness.
4. Check the gain parameters for proper settings.
5. If possible, swap the drive to troubleshoot the issue.
6. Check the motor.
Chapter 3 Practical Combat
Problem and Solution
1. The servo stops working after a period of use, or only reverses direction:
Check "d-cpo" - "lo" - "****" to see if it receives a pulse. If it is 0 or the value remains unchanged:
a. Check the pulse and direction wiring for correct operation.
b. If the host computer is a PLC, connect it to a 24V port or connect a 2K resistor in series, with the pulse and direction terminals connected separately.
c. Return the device to the factory for inspection.
a. Shielded wire of the control line:
(1). Do not connect both ends of the shielded wire;
(2). Connect the servo to the CN1 shell and the host computer to the digital ground (PLC to the power supply 0V);
(3). Connect both ends of the system shield.
b. Increase P-038 (PLC is generally = 6), save and restart;
c. Change the pulse type to AB pulse;
3. The servo motor brake is not open and may be prone to damage:
a. The brake cable must be connected to the relay. The default is normally open. Ensure correct wiring. By default, 24V is connected to the positive terminal of the relay coil, D04 is connected to the negative terminal of the relay coil, and the common point is connected to the 0V supply voltage of the switching power supply.
b. The brake cannot be used for deceleration.
4. The servo displays "T3D-**" and "STARE" upon power-on.
a. Check the power supply voltage to see if it is normal and consistent with the drive voltage.
b. Connect only the power supply, leaving the encoder and motor cables disconnected. Restart the machine and check if the display is normal. If the display is abnormal, return the machine to the factory for inspection.
a. Check the motor code.
b. Adjust the stiffness. Experienced values: P-005 = 95. P-009 = 90.
a. Check the motor code.
b. Adjust the rigidity parameters. Experienced values: P-005 = 95, P-006 = 300 (The longer the chain and belt, the higher the value). P-009 = 20, P-019 = 150 (The longer the chain and belt, the higher the value).
a. Only labels ending with R or -S have communication capabilities.
b. Ensure wiring is correct.
c. Parameters for P-181, P-182, and P-183 must be set correctly and saved to take effect after a power cycle.
d. Monitor d-rE.
rE-11: Number of communication bytes. If it is 0, communication is not established.
rE-12: Number of successful communications.
rE-13: Number of communication errors. If this value continues to increase, check the communication parameters and ensure they are consistent with those on the host computer.
e. The parameter number is the communication address; for example, the communication address for P-137 is decimal 137.
a. Parameter P-097 = 0.
b. The forward and reverse limit settings must be correctly configured. DI terminal function codes 3/4 are low-voltage normally closed signals, and -3/-4 are normally open signals.
c. If "Err7" occurs, change P-116 to 136, save the settings, and then power cycle.
a. Change P-100 to -1;
b. Use external enable;
a. Reset the motor encoder zero point as follows:
1. Change P-000 to 620.
2. Find the AF group parameters and confirm that A-fn is displayed.
3. After confirming, find fn - 2 and press and hold to confirm. The current zero point will be displayed after 1 second. A value around A0.0 will be displayed. Zero point reset is successful.
